預(yù)分支電纜主要有主干電纜、分支線、分支接頭、相關(guān)附件組成,并具有三種類型:普通型、阻燃型(ZR)、耐火型(NH)。
預(yù)分支電纜是高層建筑中母線槽供電的替代產(chǎn)品,具有供電可靠、安裝方便、防水性好,占建筑面積小、故障率低、價(jià)格便宜、免維修維護(hù)等。
預(yù)分支電纜是為配合城市高層建筑供電系統(tǒng)而開發(fā)的成套產(chǎn)品,主要用于高層建筑。
產(chǎn)品型號及名稱 TYPE & TITLE
| 型號Type | 名稱Title | |||||
| FZ-YJV | 銅芯交聯(lián)聚乙烯絕緣聚氯乙烯護(hù)套預(yù)制分支電纜 | |||||
| Cu conductor XLPE insulated PVC sheathed prefabricated branch cable | ||||||
| Z-FZ-YJV | 銅芯交聯(lián)聚乙烯絕緣聚氯乙烯護(hù)套阻燃預(yù)制分支電纜 | |||||
| Cu conductor XLPE insulated PVC sheathed flame-resistant prefabricated branch cable | ||||||
| WDZ-FZ-YJV | 銅芯交聯(lián)聚乙烯絕緣無鹵低煙聚烯烴護(hù)套阻燃預(yù)制分支電纜 | |||||
| Cu condutor XLPE insulated low smoke halogen free PE sheathed flame-resistant prefabricated branch cable | ||||||
| FZ-VV | 銅芯聚氯乙烯絕緣聚氯乙烯護(hù)套預(yù)制分支電纜 | |||||
| Cu core PVC insulated PVC sheathed prefabricated branch cable | ||||||
| Z-FZ-VV | 銅芯聚氯乙烯絕緣聚氯乙烯護(hù)套阻燃預(yù)制分支電纜 | |||||
| Cu core PVC insulated PVC sheathed flame-resistant-prefabricated branch cable | ||||||
| N-FZ-YJV | 銅芯交聯(lián)聚乙烯絕緣聚氯乙烯護(hù)套耐火預(yù)制分支電纜 | |||||
| Cu core XLPE insulated PVC sheathed PVC sheathed fire-resistant prefabricated branch cable | ||||||
主要技術(shù)參數(shù)Main Technical Parameter
| 主干電纜標(biāo)稱截面 | 分支電纜標(biāo)稱截面 | ||||||||
| main cable cross section(mm2) | Branch Cable Cross-section (mm2) | ||||||||
| 35 | 10 | 16 | 25 | - | - | - | - | - | - |
| 50 | 10 | 16 | 25 | 35 | - | - | - | - | - |
| 70 | 10 | 16 | 25 | 35 | - | - | - | - | - |
| 95 | 10 | 16 | 25 | 35 | 50 | - | - | - | - |
| 120 | 10 | 16 | 25 | 35 | 50 | 70 | - | - | - |
| 150 | 10 | 16 | 25 | 35 | 50 | 70 | - | - | - |
| 185 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | - | - |
| 240 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | - |
| 300 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
| 400 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
| 500 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
| 630 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
訂貨須知 Ordering Information
為了更好的設(shè)計(jì)您的預(yù)制分支電纜,請用戶提供以下資料:
In order to better design your prefabricated branch cable, please provide the following information:
【建筑物類別】:高層建筑,體育場館、公路等。
Building Category:high buildings,stadiums,roads.etc.
【建筑物構(gòu)造】:建筑物配電系統(tǒng)圖,預(yù)制帶分支電纜的布置。
Building Construction:building power distribution system maps,prefabricated branch cable layout.
【配電方式】:單相雙線、單相三線、三相三線、三相四線、三相五線制。
Distribution method:single-phase two –wire,single-phase three-wire,three-phase three-wire,three-phase four-wire,three-phase five-wire.
【預(yù)制帶分支電纜】:電纜型號、主干及分支電纜的截面、各分支連接盒間距離、主干電纜長度,分支電纜長度等。
Prefabricated branch cable:cable type,the section of main and branch cables,the distance between the branch junction box,length of main cable,length of branch cable.
【敷設(shè)方式】:由樓頂上拉下或從地面拉上樓頂。
Installation method:pull down from the roof to ground or pull up from the ground to roof.
【 上端支撐】:用或不用電纜懸吊裝置、電纜夾緊裝置。
Support of top: with or without cable suspension device,cable clamping device.
【 附件】:夾具、托架等。Accessories clamps,brackets,etc.
【電纜盤具】Cable tray.
【其他要求】Other requirements.
● 詳細(xì)產(chǎn)品咨詢,敬請垂詢:
使用特性:
● 絕緣電阻≥200 MΩ;
● 絕緣耐電壓3500 V/5 min不擊穿;
● 分支部接頭具有良好的氣密性與防水性,通過浸水試驗(yàn)絕緣電阻與工頻耐壓分別符合第1、第2條的要求;
● 分支接頭的接觸電阻小,接觸電阻與等長的分支線的基準(zhǔn)之比準(zhǔn)≤1.2;
● 阻燃預(yù)制分支電纜符合GB/T 12666-5成束電線電纜燃燒試驗(yàn)方法;
● 耐火預(yù)制分支電纜符合GB/T 12666-6電線電纜耐火特性試驗(yàn)方法;
● 低煙低鹵預(yù)制分支電纜:燃燒煙密度試驗(yàn)最小透光率為40%,電纜燃燒時(shí)釋出氣體的試驗(yàn)護(hù)套的鹵酸氣體總量最大100 mg/g
● 低煙無鹵預(yù)制分支電纜:燃燒煙密度試驗(yàn)最小透光率為60%,電纜燃燒時(shí)釋出氣體的試驗(yàn)護(hù)套的鹵酸氣體釋出量最大為2.0 mg/g,,護(hù)套的PH值最小為4.3,護(hù)套的電導(dǎo)率最大為10 us/mm。
● 電纜的長期允許工作溫度:聚氯乙烯絕緣為70℃;交聯(lián)聚乙烯絕緣為90℃。
● 電纜短路時(shí)(最長持續(xù)時(shí)間不超過5秒),電纜的最高溫度:聚氯乙烯絕緣為160℃;交聯(lián)聚乙烯絕緣為250℃。
● 電纜的敷設(shè)溫度應(yīng)不低于0℃。
| 交貨長度 | 運(yùn)輸 |
|
● 重量小于80kg的電纜允許成圈包裝交貨,每根成品電纜不得低于100m長度或由雙方協(xié)定任意長度交貨。 ● 允許根據(jù)協(xié)議任何長度交貨 |
●運(yùn)輸時(shí)必須將電纜牢靠的固定,以免互撞或翻倒造成對電纜或盤具的損傷 ● 防止嚴(yán)重彎曲及其他機(jī)械損傷電纜盤不許平放。 ● 運(yùn)輸中嚴(yán)禁從高處扔下裝有電纜的電纜盤 ● 電纜吊裝使用專用吊裝設(shè)備,嚴(yán)禁平吊線盤或直接從高空推卸電纜 |
| 長度誤差 | 貯存 |
|
● 長度計(jì)量誤差應(yīng)不超過±0.5% |
● 成品電纜應(yīng)存放在溫度0~40℃之間,濕度85%以下的環(huán)境中,做到不被陽光直接暴曬、被雨淋,應(yīng)適量通風(fēng),保持環(huán)境的干燥。 |
| 包裝 | 安裝須知 |
|
● 成卷或成盤電纜應(yīng)卷繞整齊,妥善包裝。電纜盤應(yīng)符合JB/T 8137-1999的規(guī)定。 ● 電纜端頭應(yīng)可靠密封,伸出盤外的電纜端頭應(yīng)加保護(hù)罩,伸出長度小于300mm ● 電纜包裝上應(yīng)附有標(biāo)簽標(biāo)明: a) 制造廠名稱及商標(biāo) b) 電纜型號及規(guī)格 c) 額定電壓 d) 長度(m) e) 重量(Kg) f) 制造日期 g) 標(biāo)準(zhǔn)編號或認(rèn)證標(biāo)識 h) 電纜盤正確旋轉(zhuǎn)方向的符號 |
● 安裝時(shí),環(huán)境溫度應(yīng)不宜低于0℃,若溫度計(jì)測試環(huán)境溫度低于0℃,應(yīng)先對電纜進(jìn)行預(yù)熱處理后再準(zhǔn)備安裝; ● 應(yīng)嚴(yán)格控制電纜敷設(shè)過程中的彎曲半徑,以免造成電纜內(nèi)部機(jī)械損傷。 ● 電纜敷設(shè)過程中如人為造成質(zhì)量事故等(如外護(hù)層損傷)應(yīng)立即修復(fù)或通知本公司售后服務(wù)部門 |